How to Save Time Locating and
Measuring Interference Current from a Foreign Line
A pipeline or cable may carry an unwanted and
sometimes unexpected current because of interference
from a foreign line, subway, or other conductor in
the vicinity of what is called our line. Corrosion
is likely where current leaves a line and enters
ground soil so we want to locate and measure the
current and find its source. A DC Amp Clamp is a
time saving tool for doing this, with improved
accuracy.
Hommema, one of our customers, has
permanently installed
Sea Clamps six feet below ground to measure
interference current flowing in a gas pipeline.
How to Measure Interference Current
Figure 1 is an idealized example of interference
[1]. Currents aiF enter our line from an anode
ground bed for a foreign line. The interference
current at one location on our line due to the
foreign anodes is measured by noting the change in
the DC Amp Clamp's reading as the connection to the
foreign rectifier is interrupted.
Figure 1
Illustrates a situation in which current aiF is entering the soil from our line as a
result of interference from a foreign line.
To measure the current at that location a
DC Amp Clip is placed on our line. The
interference current iF is the 0.3 A
difference between the "on" (+0.4 A) and
"off" (+0.1 A) current readings when an
interrupter is connected in series with the
rectifier of the foreign line.
i = 0.1 A at OFF, which may be clamp zero
offset, or current in line from another
source which is now switched.
|
The indicator's meter reads +0.4 A during the 10
second interval when the foreign rectifier is
connected by the interrupter. Then the interrupter
opens the connection to the foreign line's rectifier
for a 20 second interval. This causes the DC Amp
Clamp's meter to read +0.1 A, which could be zero
offset, current from our line's rectifier, or some
other source.
The total interference current, iF
in our line at
the particular location shown due to the foreign
line is the Peak-to-Peak current change, i.e., the
ON reading (+0.4 A) less the OFF reading (+0.1 A).
Therefore, iF = +0.3 A. This is known to be flowing
in the direction shown (anode to pipe) because the
double cabled section of the clamp is up, the bridle
is to the left [2], and the ON reading is more
positive than the OFF reading.
This says that the unwanted and perhaps
unexpected current due to the foreign line entering
our line to the left of the clamp and leaving our
line to the right of the clamp is 0.3 A.
Of course, current leaving our line may be
flowing into a resistance bond or other metallic
conductor -- not the soil. If this current equals
the maximum in our line there is no corrosion. [3]
How to Locate a Source of Interference
The interference current can usually be located
by the method shown in Figure 2 and an examination
of the territory near our line and a nearby foreign
line. In this example, the work is simplified by
discovery of a new foreign rectifier and anode
ground bed.
Figure 2
Shows the current being measured at 5
positions. |
It can be established that the foreign line is
indeed the source of interference current flowing in
our line by measuring the current in our line at
several locations on both sides of the new anode
ground bed and the foreign line.
Measurement is simpler and more accurate if the
connection can be interrupted between the foreign
line and its anodes near our line as shown in Figure
1 and 2. Most Corrosion Engineers are willing to
help do this.
The procedure shown in Figure 1 measured the
current due to the foreign line at position C on
Figure 2. This was done by measuring the
peak-to-peak change in the DC Amp Clip's meter
reading as the foreign anode connection was
interrupted.
The source of interference is located as shown in
Figure 2. In this idealized example, the current due
to the foreign line is measured at 5 positions on
our line. To make it easier to find the direction of
current flow, the double cabled half of the clamp is
always placed on top of our line, with the bridle to
the left.
At position C the current iF
is a positive
maximum of 0.3 Amp. because the DC Amp Clamp is on
our line to the right of all anode injection earth
currents aiF; and to the left of all current drains aiF to the foreign line. All interference current
from the foreign line iF
is flowing in our line at
position C.
To locate the foreign anode bed and line the
clamp is moved to find positions B and D where the
interference is half the maximum found at position
C.
At position B and D the DC Amp Clamp sees iF
=
+0.15A, i.e., the peak-to-peak difference between
the ON and Off readings of the meter on the
indicator is +0.15A, with the 10 sec ON reading more
positive than the 20 sec OFF reading. This is
because only half the interfering current is in the
pipe at these positions.
The center of the foreign rectifier anode ground
bed is opposite position B, where the interference
is half and increasingly positive as the clamp moves
toward the foreign line. The foreign line itself is
opposite position D where the interference is half,
and less positive as the clamp is moved away from
the anode bed.
Positions A & E are outside the current loop
illustrated in Figure 2, so in this idealized case
the interference current is zero. The meter on the
DC Amp Clamp will not change its reading as the
interrupter turns the foreign anode current on and
off.
However, in a real line, some anode
current is expected to flow to the left at position A; so the
real interference current will be negative at
position A. Negative current is shown on the meter
when the 10 second ON reading is more negative than
the 20 second OFF reading. There should be a short
sector of our line where the interference is zero --
to the right of A, and to the left of the earth near
the anode.
Also, in a real line the interference will
probably fan back to the foreign line for some
distance beyond position E. Then the interference at
position E will be small, and diminish slowly as the
clamp is moved to the right of E.
A DC Amp Clamp suited for measuring current in 24
to 36 inch pipes is shown in Figure 3.
Figure 3
DC Amp Clamp suited for measuring direct
current in 24 to 36 inch pipes. |
In a real situation these locations may vary. The
earth near the lines may not be of uniform
conductivity. Holidays in the insulation coating on
either line can distort the interference current
path. Fences or a third line can alter the apparent
position.
It is fortunate that foreign lines usually have
visible markers, and new rectifiers and anode beds
usually stand out on the landscape. A visual study
of the area is recommended.
The interrupter method [4] of Figure 1 is
generally accurate and usually saves time --
provided that it is only necessary to measure the
current due to the interrupted source. However, in a
real pipe line there may be currents flowing due to
several other sources.
The simplest way to measure the current due to
these other sources is to use the interrupter on
each, one at a time. If this is not feasible, the
full floating zero procedure [5] may be used to
measure the total current from all sources.
Conclusion
DC Amp Clamps can be used to save time and
improve accuracy when measuring and locating foreign
line interference.
Notes
- Figure 1 is part of the addendum October
1994 to the Swain Meter® paper of 21 Feb. 1994,
which describes DC Amp Clamps and their uses in
detail. A copy is available on request.
- How to measure the direction of flow of
current in a small cable or large pipe with a DC
Amp Clip or a DC Amp Clamp is detailed in the
Swain Meter paper of 21 Feb. 1994. Page 6 and
Figure 7 is for Clamps.
- I am an instrument maker, not a Corrosion
Engineer. Our customers may well know how to use
our Clamp-On Ammeters to solve corrosion
problems better than I do. I state what I think
after talking with customers.
- The use of a current interrupter is
discussed on page 11 of the Swain Meter paper.
Figure 11 shows how to measure flange current.
- ibid., page 12 for the full floating zero
procedure.
|